Supply | |
---|---|
Rated voltage | 3.6 V DC , battery operated |
Power dissipation/power consumption | < 0.09 W |
Input | |
Connection | terminals 1, 2, 3, 4 |
RTD | type Pt100, Pt1000 (IEC 751: 1995; GOST: alpha = 0.391) |
Thermocouples | type E, J, K, T (IEC584-1) |
Resistor | |
Voltage | mV Input |
Input resistance | ? 1 M? |
Output | |
Output variables | PV: input 1 (°C, ?, mV) SV: input 2 (°C, ?, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%) |
Transfer characteristics | |
Accuracy | - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3) - external cold junction compensation error ± 1 °C (typ.) - resolution error < 0.1 °C - accuracy TC ± 20 µV - accuracy RTD: ± 100 m? |
Indicators/settings | |
Parameter assignment | - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes |
Directive conformity | |
Electromagnetic compatibility | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
Conformity | |
Degree of protection | IEC 60529 |
Accuracy | IEC 61298-3 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -20 ... 70 °C (-4 ... 158 °F) |
Corrosion resistance | acc. to ISA-S71.04-1985, severity levelG3 test setup and execution acc. to EN60068-2-60 |
Mechanical specifications | |
Degree of protection | IP65 |
Mass | approx. 1000 g |
Dimensions | 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch) |
Mounting | panel or pole mounting |
Data for application in connection with hazardous areas | |
EC-Type Examination Certificate | IMQ 09 ATEX 008X |
Directive conformity | |
International approvals | |
FM approval | CoC 3042534 |
IECEx approval | IECEx INE 09.0025X |
Accessories | |
Designation | battery W-BAT-B1Или отправьте нам запрос наnnection with hazardous areas (order separately) Mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |