AS-Interface I/O module VBA-4E3A-G20-ZEL/E2L-P5 - фото 1 - id-p95198894
Характеристики и описание

Техническая спецификация в PDF  

Описание оборудования

G20 module
4 inputs/3 outputs

General specifications

Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification? V2.1
UL File NumberE223772 "For use in NFPA 79 Applications only"
MTBF110 a

Indicators/operating means

LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 3 LED yellow

Electrical specifications

Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current? 35 mA

Input

Number/Type4 Inputs for 3-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Current loading capacity500 mA , overload and short-circuit protected
Input current? 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2
0 (undamped) ?0.5mA
1 (damped) ?2.0mA
Signal delay< 1 ms (input/AS-Interface)

Output

Number/Type3 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current2 A per output
TB ? 40°C: 6A total
TB ? 60°C: OUT1+OUT2 max. 3A, OUT3 max. 2A
Voltage? (UAUX - 0.5V)

Directive conformity

Electromagnetic compatibility

Standard conformity

Degree of protectionEN60529:2000
Fieldbus standardEN62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN61000-6-4:2007
AS-InterfaceEN62026-2:2013
Noise immunityEN61000-6-2:2005, EN61326-1:2006, EN62026-2:2013

Programming instructions

ProfileS-7.A.E
IO code7
ID codeA
ID1 code7
ID2 codeE
Data bits (function via AS-Interface) input output
Parameter bits (programmable via AS-i)function

Ambient conditions

Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)

Mechanical specifications

Degree of protectionIP54 according to EN 60529
ConnectionAS-Interface, A