Описание оборудования | |
---|---|
KE switch cabinet module 4 inputs (PNP) | |
General specifications | |
Slave type | A/B slave |
AS-Interface specification | V3.0 |
Required master specification | ? V2.0 |
UL File Number | E223772 |
Indicators/operating means | |
LED FAULT | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
LED INT | Internal input supply active; LED green |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
LED IN | switching state (input); 4 LED yellow |
Electrical specifications | |
Auxiliary voltage (input) | 12 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ? 30 mA (without sensors) / max. 180 mA |
Protection class | III |
Surge protection | UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) |
Input | |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
Voltage | 21 ... 31 V DC (INT) |
Current loading capacity | ? 150 mA, overload- and short-circuit protected (INT) |
Input current | ? 9 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
Signal delay | < 1 ms (input/AS-Interface) |
Directive conformity | |
Electromagnetic compatibility | |
Standard conformity | |
Degree of protection | EN60529:2000 |
Fieldbus standard | EN62026-2:2013 |
Input | EN 61131-2:2004 |
Emitted interference | EN 61000-6-4:2007 |
AS-Interface | EN62026-2:2013 |
Noise immunity | EN61000-6-2:2005, EN61326-1:2006, EN62026-2:2013 |
Programming instructions | |
Profile | S-0.A.0 |
IO code | 0 |
ID code | A |
ID1 code | 7 |
ID2 code | 0 |
Data bits (function via AS-Interface) | input output |
Parameter bits (programmable via AS-i) | function |
Ambient conditions | |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ? 2000 m above MSL |
Pollution degree | 2 |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25mm2...2.5mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5mm2...1.5mm2 |