Описание оборудования | |
---|---|
G11 module 4 inputs and 4 outputs | |
General specifications | |
Slave type | Standard slave |
AS-Interface specification | V3.0 |
Required master specification | ? V2.1 |
UL File Number | E223772 |
Indicators/operating means | |
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply i.e. overload or lead interruption outputs |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
LED IN | switching state (input); 4 LED yellow |
LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
Electrical specifications | |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Rated operating voltage | 18,0 ... 31.6 V from AS-Interface |
Rated operating current | ? 40 mA (without sensors) / max. 240 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input | |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 12 ... 31 V |
Current loading capacity | ? 200 mA, overload and short-circuit protected |
Input current | ? 9 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
Signal delay | < 1 ms (input/AS-Interface) |
Output | |
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Current | 2 A per output TB ? 40 °C: 6 A total TB ? 70 A°C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A |
Voltage | ? (UAUX - 0.5 V) |
Galvanic isolation | |
Input/Output | safe isolation, rated insulation voltage 40 V DC |
Output/AS-Interface | safe isolation, rated insulation voltage 40 V DC |
Directive conformity | |
Electromagnetic compatibility | |
Standard conformity | |
Degree of protection | EN60529:2000 |
Fieldbus standard | EN62026-2:2013 |
Input | EN 61131-2:2007 |
Emitted interference | EN61000-6-4:2007 |
AS-Interface | EN62026-2:2013 |
Noise immunity | EN61000-6-2:2005, EN61326-1:2006, EN62026-2:2013 |
Programming instructions | |
Profile | S-7.F |
IO code | 7 |
ID code | F |
ID1 code | F |
ID2 code | E |
Data bits (function via AS-Interface) | input output |
Parameter bits (programmable via AS-i) | function |
Ambient conditions | |
Ambient temperature |