| Technical data | EP3162-0002 |
|---|
| Number of inputs | 2 (single-ended) |
| Input connections | M12, screw type |
| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, shielded, screw type |
| Signal type | -10/0…+10 V | -20/0/4…+20 mA |
| Internal resistance | > 200 kΩ | typ. 85 Ω + diode voltage |
| Common-mode voltage UCM | max. 35 V |
| Resolution | 16 bit (incl. sign) |
| Measuring error | < ±0.3="" %="" (relative="" to="" full="" scale=""> |
| Input filter limit frequency | 5 kHz |
| Conversion time | ~ 100 µs |
| Nominal voltage | 24 V DC (-15 %/+20 %) |
| Distributed clocks | yes |
| Input filter | configurable |
| Sensor supply | UA from US, electrically isolated |
| Current consumption from US | 120 mA |
| Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
| Bit width in the process image | 2 x 16 bit input, 2 x 8 bit status |
| Electrical isolation | 500 V fieldbus, 300 V signals/signal |
| Special features | galvanic isolation of the channels |
| Weight | approx. 165 g |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
| Approvals | CE, UL |